Ex9M2M 250A Motor Circuit Protectors
Motor-Circuit Protectors
NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty.
Unit of Measure
Items |
/Asset/a1188.jpg M2MS250T3 Ex9 Series M2M, S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/a1188.jpg M2MN250T3 Ex9 Series M2M, N Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/MCP---face.jpg M2MH250T3 Ex9 Series M2M, H Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/MCP---face.jpg M2MS250T3L Ex9 Series M2M, S Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
/Asset/MCP---face.jpg M2MN250T3L Ex9 Series M2M, N Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
|||||
Description | N/A NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty. | |||||||||
Brands | N/A NOARK® | |||||||||
Continuous Current | N/A 250 A | |||||||||
Cam Setting | N/A A B C D E F G | |||||||||
Full Load Current at Cam Setting A | N/A 96.2 to 115.3 A | |||||||||
Full Load Current at Cam Setting B | N/A 115.4 to 134.5 A | |||||||||
Full Load Current at Cam Setting C | N/A 134.6 to 153.7 A | |||||||||
Full Load Current at Cam Setting D | N/A 153.8 to 173.0 A | |||||||||
Full Load Current at Cam Setting E | N/A 173.1 to 192.2 A | |||||||||
Full Load Current at Cam Setting F | N/A 192.3 to 211.4 A | |||||||||
Full Load Current at Cam Setting G | N/A 211.5 to 217.6 A | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting A | N/A 1250 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting B | N/A 1500 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting C | N/A 1750 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting D | N/A 2000 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting E | N/A 2250 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting F | N/A 2500 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting G | N/A 2750 | |||||||||
Rated Current at 480 Alternating Current (AC) Voltage | N/A 35 kA | N/A 65 kA | N/A 100 kA | N/A 35 kA | N/A 65 kA | |||||
Connection Type | N/A S Interrupting - Bus Bar Connection | N/A N Interrupting - Bus Bar Connection | N/A H Interrupting - Bus Bar Connection | N/A S Interrupting - Lug Line/Load Side Connection | N/A N Interrupting - Lug Line/Load Side Connection | |||||
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|
|||||||||
Certifications |
N/A
|
|||||||||
Note | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | |||||
|