Ex9M3M 400A Motor Circuit Protectors
Motor-Circuit Protectors
NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty.
Unit of Measure
Items |
/Asset/a1191.jpg M3MS400T3 Ex9 Series M3M, S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/a1191.jpg M3MN400T3 Ex9 Series M3M, N Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/a1191.jpg M3MH400T3 Ex9 Series M3M, H Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
/Asset/a1192.jpg M3MS400T3L Ex9 Series M3M, S Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
/Asset/a1192.jpg M3MN400T3L Ex9 Series M3M, N Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
|||||
Description | N/A NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty. | |||||||||
Brands | N/A NOARK® | |||||||||
Continuous Current | N/A 400 A | |||||||||
Cam Setting | N/A A B C D E F G | |||||||||
Full Load Current at Cam Setting A | N/A 153.8 to 184.5 A | |||||||||
Full Load Current at Cam Setting B | N/A 184.6 to 215.3 A | |||||||||
Full Load Current at Cam Setting C | N/A 215.4 to 246.0 A | |||||||||
Full Load Current at Cam Setting D | N/A 246.1 to 276.8 A | |||||||||
Full Load Current at Cam Setting E | N/A 276.9 to 307.6 A | |||||||||
Full Load Current at Cam Setting F | N/A 307.7 to 338.4 A | |||||||||
Full Load Current at Cam Setting G | N/A 338.5 to 348.1 A | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting A | N/A 2000 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting B | N/A 2400 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting C | N/A 2800 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting D | N/A 3200 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting E | N/A 3600 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting F | N/A 4000 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting G | N/A 4400 | |||||||||
Rated Current at 480 Alternating Current (AC) Voltage | N/A 42 kA | N/A 65 kA | N/A 100 kA | N/A 42 kA | N/A 65 kA | |||||
Connection Type | N/A S Interrupting - Bus Bar Connection | N/A N Interrupting - Bus Bar Connection | N/A H Interrupting - Bus Bar Connection | N/A S Interrupting - Lug Line/Load Side Connection | N/A N Interrupting - Lug Line/Load Side Connection | |||||
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|
|||||||||
Certifications |
N/A
|
|||||||||
Note | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | |||||
|