Print Back
Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Unit of Measure
Items Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD93A32
Ex9RD Series 23 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD93A40
Ex9RD Series 30 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD93A50
Ex9RD Series 37 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD93A65
Ex9RD Series 48 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD Series 28 Ampere (A) Minimum Current Thermal Overload Relay
Ex9RD93A70
Ex9RD Series 55 Ampere (A) Minimum Current Thermal Overload Relay
Description N/A
Brands N/A NOARK®
Function N/A Overload Thermal
Minimum Current N/A 23 A N/A 30 A N/A 37 A N/A 48 A N/A 55 A
Maximum Current N/A 32 A N/A 40 A N/A 50 A N/A 65 A N/A 70 A
Matched Fuse (aM) N/A 40 N/A 40 N/A 63 N/A 63 N/A 80
Matched Fuse (gG) N/A 63 N/A 100 N/A 100 N/A 100 N/A 125
Current N/A 93 A
Compensation Temperature N/A -13 to 131 ºF-25 to +55 ºC
Use with Contactors N/A Ex9CD40~95
Certifications N/A
  • UL Listed, File Number E353865
  • Certified for Canada According to CSA Standards
  • IEC/EN 60947-4-1
  • CE Compliant
Features N/A
  • Rated current up to 630 A at 600 Vac, 50/60 Hz
  • Overload protection trip Class 10 A
  • Phase loss sensitivity
  • Adjustable current setting for overload protection
  • Automatic or manual reset selectable
  • Trip-free mechanism
  • Status indication
  • STOP and TEST function
  • Direct mount to contactors or 35 mm DIN rail mounting base option