M4MS600T3 Ex9 Series M4M, S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M4MN600T3 Ex9 Series M4M, N Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M4MH600T3 Ex9 Series M4M, H Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M4MS600T3L Ex9 Series M4M, S Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
M4MN600T3L Ex9 Series M4M, N Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
|||||
Description | N/A NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty. | |||||||||
Brands | N/A NOARK® | |||||||||
Continuous Current | N/A 600 A | |||||||||
Cam Setting | N/A A B C D E F G | |||||||||
Full Load Current at Cam Setting A | N/A 230.8 to 276.8 A | |||||||||
Full Load Current at Cam Setting B | N/A 276.9 to 323.0 A | |||||||||
Full Load Current at Cam Setting C | N/A 323.1 to 369.0 A | |||||||||
Full Load Current at Cam Setting D | N/A 369.2 to 415.3 A | |||||||||
Full Load Current at Cam Setting E | N/A 415.4 to 461.4 A | |||||||||
Full Load Current at Cam Setting F | N/A 461.5 to 507.6 A | |||||||||
Full Load Current at Cam Setting G | N/A 507.7 to 522.2 A | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting A | N/A 3000 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting B | N/A 3600 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting C | N/A 4200 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting D | N/A 4800 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting E | N/A 5400 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting F | N/A 6000 | |||||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting G | N/A 6600 | |||||||||
Rated Current at 480 Alternating Current (AC) Voltage | N/A 42 kA | N/A 65 kA | N/A 100 kA | N/A 42 kA | N/A 65 kA | |||||
Connection Type | N/A S Interrupting - Bus Bar Connection | N/A N Interrupting - Bus Bar Connection | N/A H Interrupting - Bus Bar Connection | N/A S Interrupting - Lug Line/Load Side Connection | N/A N Interrupting - Lug Line/Load Side Connection | |||||
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|
|||||||||
Certifications |
N/A
|
|||||||||
Note | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | |||||
|