Items |
M6MS1200E3F Ex9 Series M6M, S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M6MN1200E3F Ex9 Series M6M, N Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M6MS1200E3LF Ex9 Series M6M, S Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
M6MN1200E3LF Ex9 Series M6M, N Interrupting - Lug Line/Load Side Connection Molded Case Motor Circuit Protector |
||||
Description | N/A NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty. | |||||||
Brands | N/A NOARK® | |||||||
Continuous Current | N/A 1200 A | |||||||
Cam Setting | N/A 10 12 2 3 4 6 8 | |||||||
Full Load Current at Cam Setting 2 | N/A 184.6 to 276.8 A | |||||||
Full Load Current at Cam Setting 3 | N/A 276.9 to 369.1 A | |||||||
Full Load Current at Cam Setting 4 | N/A 369.2 to 553.7 A | |||||||
Full Load Current at Cam Setting 6 | N/A 553.8 to 738.4 A | |||||||
Full Load Current at Cam Setting 8 | N/A 738.5 to 923.0 A | |||||||
Full Load Current at Cam Setting 10 | N/A 923.1 to 1107.6 A | |||||||
Full Load Current at Cam Setting 12 | N/A 1107.7 to 1309.1 A | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 2 | N/A 2400 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 3 | N/A 3600 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 4 | N/A 4800 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 6 | N/A 7200 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 8 | N/A 9600 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 10 | N/A 12000 | |||||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting 12 | N/A 14400 | |||||||
Rated Current at 480 Alternating Current (AC) Voltage | N/A 42 kA | N/A 65 kA | N/A 42 kA | N/A 65 kA | ||||
Connection Type | N/A S Interrupting - Bus Bar Connection | N/A N Interrupting - Bus Bar Connection | N/A S Interrupting - Lug Line/Load Side Connection | N/A N Interrupting - Lug Line/Load Side Connection | ||||
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|
|||||||
Certifications |
N/A
|
|||||||
Note | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs. | ||||
|