Brands |
N/A NOARK® |
Continuous Current |
N/A 600 A |
Cam Setting |
N/A A B C D E F G |
Full Load Current at Cam Setting A |
N/A 230.8 to 276.8 A |
Full Load Current at Cam Setting B |
N/A 276.9 to 323.0 A |
Full Load Current at Cam Setting C |
N/A 323.1 to 369.0 A |
Full Load Current at Cam Setting D |
N/A 369.2 to 415.3 A |
Full Load Current at Cam Setting E |
N/A 415.4 to 461.4 A |
Full Load Current at Cam Setting F |
N/A 461.5 to 507.6 A |
Full Load Current at Cam Setting G |
N/A 507.7 to 522.2 A |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting A |
N/A 3000 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting B |
N/A 3600 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting C |
N/A 4200 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting D |
N/A 4800 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting E |
N/A 5400 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting F |
N/A 6000 |
Motor Circuit Protection (MCP) Trip Setting at Cam Setting G |
N/A 6600 |
Rated Current at 480 Alternating Current (AC) Voltage |
N/A 100 kA |
Connection Type |
N/A H Interrupting - Lug Line/Load Side Connection |
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|