Print Back
NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty.
Unit of Measure

Specifications

Brands

N/A NOARK®

Continuous Current

N/A 800 A

Cam Setting

N/A A B C D E F G

Full Load Current at Cam Setting A

N/A 307.7 to 369.1 A

Full Load Current at Cam Setting B

N/A 369.2 to 430.7 A

Full Load Current at Cam Setting C

N/A 430.8 to 492.2 A

Full Load Current at Cam Setting D

N/A 492.3 to 553.7 A

Full Load Current at Cam Setting E

N/A 553.8 to 615.3 A

Full Load Current at Cam Setting F

N/A 615.4 to 676.8 A

Full Load Current at Cam Setting G

N/A 676.9 to 738.5 A

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting A

N/A 4000

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting B

N/A 4800

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting C

N/A 5600

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting D

N/A 6400

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting E

N/A 7200

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting F

N/A 8000

Motor Circuit Protection (MCP) Trip Setting  at Cam Setting G

N/A 8800

Rated Current at 480 Alternating Current (AC) Voltage

N/A 42 kA

Connection Type

N/A S Interrupting - Lug Line/Load Side Connection

Features

Features

N/A The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching.
In particular, when selecting these devices, different factors must be taken into consideration, such as:
  • The motor power
  • The diagram and type of starting
  • The type of motor: with cage rotor or with wound rotor
  • The fault current at the point of the network where the motor is installed

Certifications

Certifications

N/A
  • UL 489 Recognized, File Number E355392 (Standard for connection terminals which allows the user to apply field wiring directly to the breaker)
  • Certified for Canada According to CSA Standards 22.2 No.5
  • IEC/EN 60947-2
  • CE Compliant
  • RoHS Compliant

Note

Note

N/A Lug Line/Load Side Connection MCP sold with Terminal Lugs.