Items |
M1MS03T3 Ex9 Series M1M, 3 Ampere (A) Continuous Current S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M1MS07T3 Ex9 Series M1M, 7 Ampere (A) Continuous Current S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M1MS15T3 Ex9 Series M1M, 15 Ampere (A) Continuous Current S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M1MS30T3 Ex9 Series M1M, 30 Ampere (A) Continuous Current S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
M1MS50T3 Ex9 Series M1M, 50 Ampere (A) Continuous Current S Interrupting - Bus Bar Connection Molded Case Motor Circuit Protector |
|||||
Description | N/A NOARK® Electric offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty. | |||||||||
Brands | N/A NOARK® | |||||||||
Continuous Current | N/A 3 A | N/A 7 A | N/A 15 A | N/A 30 A | N/A 50 A | |||||
Cam Setting | N/A A B C D E | N/A A B C D E F | N/A A B C D E F | N/A A B C D E F G | N/A A B C D E F G | |||||
Full Load Current at Cam Setting A | N/A 1.6 to 1.7 A | N/A 2.7 to 3.1 A | N/A 5.7 to 6.8 A | N/A 11.5 to 13.7 A | N/A 19.2 to 22.9 A | |||||
Full Load Current at Cam Setting B | N/A 1.8 to 1.9 A | N/A 3.2 to 3.6 A | N/A 6.9 to 7.9 A | N/A 13.8 to 16 A | N/A 23.0 to 26.8 A | |||||
Full Load Current at Cam Setting C | N/A 2.0 to 2.2 A | N/A 3.7 to 4.2 A | N/A 8 to 9.1 A | N/A 16.1 to 18.3 A | N/A 26.9 to 30.6 A | |||||
Full Load Current at Cam Setting D | N/A 2.3 to 2.4 A | N/A 4.3 to 4.7 A | N/A 9.2 to 10.3 A | N/A 18.4 to 20.6 A | N/A 30.7 to 34.5 A | |||||
Full Load Current at Cam Setting E | N/A 2.5 to 2.6 A | N/A 4.8 to 5.2 A | N/A 10.4 to 11.4 A | N/A 20.7 to 22.9 A | N/A 34.6 to 38.3 A | |||||
Full Load Current at Cam Setting F | N/A | N/A 5.3 to 5.8 A | N/A 11.5 to 12.6 A | N/A 23 to 25.2 A | N/A 38.4 to 42.1 A | |||||
Full Load Current at Cam Setting G | N/A | N/A | N/A | N/A 25.3 to 26.1 A | N/A 42.2 to 43.5 A | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting A | N/A 21 | N/A 35 | N/A 75 | N/A 150 | N/A 250 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting B | N/A 24 | N/A 42 | N/A 90 | N/A 180 | N/A 300 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting C | N/A 27 | N/A 49 | N/A 105 | N/A 210 | N/A 350 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting D | N/A 30 | N/A 56 | N/A 120 | N/A 240 | N/A 400 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting E | N/A 33 | N/A 63 | N/A 135 | N/A 270 | N/A 450 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting F | N/A | N/A 70 | N/A 150 | N/A 300 | N/A 500 | |||||
Motor Circuit Protection (MCP) Trip Setting at Cam Setting G | N/A | N/A | N/A | N/A 330 | N/A 550 | |||||
Rated Current at 480 Alternating Current (AC) Voltage | N/A 35 kA | |||||||||
Rated Current at 240 Alternating Current (AC) Voltage | N/A | |||||||||
Connection Type | N/A S Interrupting - Bus Bar Connection | |||||||||
Features |
N/A
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching. In particular, when selecting these devices, different factors must be taken into consideration, such as:
|
|||||||||
Certifications |
N/A
|
|||||||||
Note | N/A Bus Bar Connection MCP not sold with (Bus Bar Connection not available through NOARK® Electric) or Terminal Lugs. | |||||||||
|